Profibus PA

E488020

Profibus PA is an industrial fieldbus standard designed for process automation, enabling digital communication and power over a two-wire bus for smart field devices in hazardous and non-hazardous environments.

Try in SPARQL Jump to: Surface forms Statements Referenced by

Observed surface forms (1)

Surface form Occurrences
PROFIBUS 1

Statements (49)

Predicate Object
instanceOf digital communication protocol
industrial fieldbus standard
process automation network
applicationDomain chemical industry
oil and gas industry
pharmaceutical industry
power generation plants
water and wastewater treatment
basedOn PROFIBUS DP protocol NERFINISHED
compatibleWith PROFIBUS DP via segment couplers
PROFIBUS DP/PA links NERFINISHED
competesWith FOUNDATION Fieldbus H1 NERFINISHED
HART over 4–20 mA
dataRate 31.25 kbit/s
developedBy PNO NERFINISHED
PROFIBUS Nutzerorganisation e.V. NERFINISHED
enables advanced diagnostics in process plants
centralized configuration of field devices
remote parameterization of instruments
fullName Process Field Bus Process Automation
governedBy PROFIBUS and PROFINET International NERFINISHED
medium twisted pair cable
partOf IEC 61158 fieldbus standards NERFINISHED
PROFIBUS family NERFINISHED
physicalLayerStandard IEC 61158-2 NERFINISHED
provides power supply to field devices via bus
safetyFeature intrinsic safety concepts such as FISCO
standardizedBy IEC 61158 NERFINISHED
IEC 61784 NERFINISHED
supports acyclic data exchange
cyclic data exchange
diagnostic information from field devices
digital communication over two-wire bus
hazardous area installations
intrinsically safe operation
non-hazardous area installations
simultaneous power and data on same pair
supportsDeviceTypes flow meters
level transmitters
pressure transmitters
temperature transmitters
valve positioners
topology bus topology
tree topology with spurs
usedFor connection of smart field devices
measurement and control in process industries
process automation
uses MBP-IS physical layer for intrinsic safety
Manchester Bus Powered physical layer

Referenced by (2)

Full triples — surface form annotated when it differs from this entity's canonical label.

SCADA systems commonlyUsesProtocol Profibus PA
this entity surface form: PROFIBUS